B75C

Emergency Lighting Equipment



One-lamp emergency illumination; For higher wattage 4-pin compact lamps (without integral starters); Suitable forlow mercury (green) lamps


Product Summary

  • UL Listed
    Factory or Field Installation
    (Indoor and Damp)
  • Illumination Time
    90 Minutes
  • Initial Light Output
    600 - 1300 Lumens
  • Full Warranty
    3 Years (NOT pro-rata)
  • Voltage
    120/277 VAC, 60 Hz
  • AC Input Current
    300 mA
  • AC Input Power Rating
    4.0 Watts
  • Test Switch
    Single Pole
  • Battery
    High-Temperature, Maintenance-Free
    Nickel-Cadmium Battery
    7- to 10-Year Life Expectancy
  • Battery Charging Current
    300 mA
  • Recharge Time
    24 Hour
  • Charging Indicator Light
    LED
  • Temperature Rating (Ambient)
    0°C to +50°C (32°F to 122°F)
  • Dimensions
    13.3" x 2.5" x 1.5"
    (338 mm x 63 mm x 38 mm)
    2' (610 mm) Flex Conduit Each End
    Mounting Center 12.8" (325 mm)
  • Weight
    3.5 lbs. (1.6 kg)

Philips Bodine B75C Emergency Ballast
UL LISTEDAvailable lamps


  Downloads

Spec Sheet Spec
Sheet
Spec Sheet

Instruction Sheet