ELI-S-400

Emergency lighting inverter



Sinusoidal (Sine Wave) Output
400 VA Power Maximum


Product Summary

  • ETL Listed
    UL924 Emergency Lighting Compliant
    Field Installation
  • Illumination Time
    90 Minutes
  • Maximum Load Power
    400 VA
  • Full Warranty
    1 year full, 4 years pro-rata
  • Input
    • Input voltage: 120 or 277VAC
    • Input frequency: 60 Hz
    • Synchronizing slew rate: 1 Hz per second nominal
    • Input surge protection: Meets UL 924
  • Output
    • Output voltage: 120 or 277VAC, 60Hz
    • Output regulation: (static) ± 5% based on a 0 - 100% resistive load
    • Output distortion: Less than 3% THD linear load
    • Load Power Factor: .5 lag to .5 lead
    • Output frequency: Normally, Synchronized to utility, ± 2 Hz during emergency
    • Overload: 150% for five seconds
    • Time to transfer to inverter after a utility power failure: 50 ms.
  • Battery Type
    Maintenance-Free Sealed Lead Calcium
  • Recharge Time
    Less than 168 Hours (meets UL924)
  • Battery Protection
    Automatic low-battery voltage disconnect and reverse polarity protection. Automatic restart upon utility return
  • Temperature Rating
    68°F to 86°F (20°C to 30°C)
  • Dimensions
    18”W x 8”D x 15”H
  • Weight
    98 lbs (44.4 kg)

Philips Bodine ELI-S-400 Inverter
UL LISTED

Downloads

Technical Data Sheets


Product Data sheets Spec SheetInstructions